BP52 Alarm Panel
NEW ALARMS
BP52 Alarm Panel
NEW ALARMS
The BP52 Alarm Panel is the central brain of a Verkada alarm system. With 32 alarm zones, it can easily replace traditional panels and take over existing sensors without new wiring.
Complete coverage
With 32 zones, 4 RS485 outputs, and 2 relay outputs, the BP52 can replace any panel and take over existing wired sensors and devices.
Highly available
Easily add battery packs and LTE backup to keep the system online during outages.
Cloud-Managed
Manage your alarm system from any device, anywhere. No need to be on site.
Built for scale
Leverage expanders to consolidate faraway sensors into a single RS485 cable run to the panel. Create software-defined partitions to independently arm different areas.
Automatic health checks
Instead of paying add-on fees for daily health checks, you can see the health of your system at any time in Command.
Real-time alerts
Receive notifications in the event that a sensor or device goes offline -- no more silent failures.
Always included
Cloud management via Command
10-year warranty
Automatic firmware updates
Alerts for offline devices
Product Specifications
Power and network
Power Consumption
175W max
See Output Specifications table in datasheet
Connectivity
100/1000 Mbps RJ45 port,
USB 2.0 (for ACC-CEL-LTE-2),
VLink sub-GHz transceiver
Power Input
100-240V AC (50-60Hz)
2x battery slots (for ACC-VBX-200WH)
2x VBX ports (for ACC-VBX-ENC)
Wireless Communication
VLink (proprietary 868-928 MHz)
Wireless Range
300 ft / 90 m (line of sight)1
Inputs and outputs
Alarm Inputs
32x inputs with 12V DC aux power
Compatible with variable EOL resistors
(1kΩ - 4.7kΩ)
Relay Outputs
2x relays for siren/strobe/NAC with switch-selectable voltage & optional dry config:
· 12 or 24V DC wet operation
· 24V DC dry operation
Conventional Fire Input (IDC)2
2x 2-wire or 2x 4-wire Initiating Device Circuit inputs (conventional) with switch-selectable 12/24V DC aux power
Note: IDC inputs share a single switch for voltage selection
Addressable Fire Input (SLC)2
2x 2-wire Signaling Line Circuit inputs
(addressable) with 36V DC aux power
RS485 Outputs
4x RS485 outputs with 36V DC aux power
PoE Outputs
4x PoE+ / 802.3at capable ports
60W total power budget
Tamper Detection
Yes
General
Dimensions
Height: 21.9" (55.7 cm)
Width: 12.7" (32.3 cm)
Depth: 4.6" (11.6 cm)
Operating Temperature and Humidity
32 to 122° F (0 to 50° C)
0-90% RH non-condensing
Weight
16.2 lb (7.3 kg)
Warranty
10 years
Certifications
FCC, IC, CE, UKCA, RCM, CEC BC, UL Safety
Installation
Included Accessories
AC cable, VLink antenna, 32x 1kΩ EOL resistors, wall mount, 2x keys, flathead screwdriver, 4x plywood screws
Mounting Options
Wall mount
For compliance and regional availability, please see https://www.verkada.com/alarms-availability/
1. Real-world range depends on a variety of factors
2. Future software support
Accessories
Provides LTE backup connectivity the BP52 Alarm Panel
Allows for two additional backup batteries to be connected to the BP52 Alarm Panel
Resources
Get a Live Demo
See Verkada Alarms in action and learn how it can meet the unique needs of your organization.